64861

MICROLOGIC6.0P TRIP

Trade Price

POA

Per

1

Unit

EA

Pack Quantity

1

64861

Technical Specifications

Range

MasterPact

Range of product

MasterPact NW UL 489

Product or component type

Control unit

Trip unit name

MicroLogic 6.0 P

Trip unit technology

Electronic

Range compatibility

Masterpact NW08...50 UL 489

Device application

Distribution

Number of poles

3P 4P

Protected poles description

4t 3t 3t + N/2

Trip unit protection functions

Selective + earth-fault protection

Protection type

for overload protection (long time) for short time short-circuit protection for instantaneous short-circuit protection for earth fault

Trip unit rating

800 A at 50 °C 1200 A at 50 °C 1600 A at 50 °C 2000 A at 50 °C 2500 A at 50 °C 3000 A at 50 °C 4000 A at 50 °C 5000 A at 50 °C

Network type

AC

Network frequency

50/60 Hz

Circuit breaker mounting mode

Drawout

Long-time pick-up adjustment type Ir (thermal protection)

Adjustable 9 settings

[Ir] long-time protection pick-up adjustment range

0.4...1 x In

Long-time protection delay adjustment type tr

Adjustable 9 settings

[tr] long-time protection delay adjustment range

0.7…16.6 s at 7.2 x Ir 0.7…24 s at 6 x Ir 12.5…600 s at 1.5 x Ir

Thermal memory

20 mn

Short-time protection pick-up adjustment type Isd

Adjustable 9 settings

[Isd] Short-time protection pick-up adjustment range

1.5...10 x Ir

Short-time protection delay adjustment type tsd

Adjustable

[tsd] Short-time protection delay adjustment range

0…0.4 s I²t=off 0.1…0.4 s I²t=on

Instantaneous protection pick-up adjustment type Ii

Adjustable 9 settings

[Ii] instantaneous protection pick-up adjustment range

Off 2...15 x In

Ground-fault protection pick-up adjustment type Ig

Adjustable 9 settings

[Ig] ground-fault protection pick-up adjustment range

0.2...1 x In for 400 A < In < 1250 A 0.3...1 x In for In <= 400 A 500...1200 A for In >= 1250 A

Ground-fault protection time delay adjustment type tg

Adjustable

[tg] ground-fault protection time delay adjustment range

0…0.4 s I²t=off 0.1…0.4 s I²t=on

earth-leakage protection

Without

Zone selective interlocking ZSI

With

Local signalling

3 LEDs (red) for electrical fault 1 LED (red) for internal error

Display type

Digital display

Type of measurement

Power meter

communication of data

Measurement readout Protection and alarm settings Maintenance indicators

standards

UL 489

Ambient air temperature for operation

-25…70 °C

Ambient air temperature for storage

-40…85 °C

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

5.5 cm

Package 1 Width

5.0 cm

Package 1 Length

220.0 cm

Package 1 Weight

600.0 g

Warranty

18 months

Document Links

Datasheet