47288

TRIP UNIT MICROLOGIC 6.0 E FOR MASTERPAC

Trade Price

£2,622.89

Per

1

Unit

EA

Pack Quantity

1

47288

Information

Micrologic 6.0E (Energy meter) is an electronic control unit used on Masterpact NT 06 to 16 and Masterpact NW 08 to 63 fixed circuit breakers. This control unit has a selective and earth fault protection (LSIG) and is designed to protect power circuits and loads. It embeds adjustable long time protection against overloads. It provides also adjustable short-time protection and instantaneous protection against short-circuits. Micrologic 6.0E offers an adjustable earth fault protection. Micrologic 6.0E indicates overloads with an Alarm LED. It is able to display the trip cause through 3 others LEDs. Micrologic 6.0E is equipped with a digital LCD screen that displays the active energy with 2% accuracy. This control unit can be associated with fixed Masterpact NT and NW basic frame.

Technical Specifications

Range

MasterPact

Range of product

MasterPact NW MasterPact NT

Product or component type

Control unit

Trip unit name

MicroLogic 6.0 E

Trip unit technology

Electronic

Range compatibility

Masterpact NT06...16 Masterpact NW08...40 Masterpact NW40b...63

Device application

Distribution

Number of poles

4P 3P

Protected poles description

4t 3t 3t + N/2

Trip unit protection functions

Selective + earth-fault protection

Protection type

for overload protection (long time) for short time short-circuit protection for instantaneous short-circuit protection for earth fault

Trip unit rating

630 A at 50 °C 800 A at 50 °C 1000 A at 50 °C 1250 A at 50 °C 1600 A at 50 °C 2000 A at 50 °C 2500 A at 50 °C 3200 A at 50 °C 4000 A at 50 °C 5000 A at 50 °C 6300 A at 50 °C

Network type

AC

Network frequency

50/60 Hz

Circuit breaker mounting mode

Fixed

Long-time pick-up adjustment type Ir (thermal protection)

Adjustable 9 settings

[Ir] long-time protection pick-up adjustment range

0.4...1 x In

Long-time protection delay adjustment type tr

Adjustable 9 settings

[tr] long-time protection delay adjustment range

0.7…16.6 s at 7.2 x Ir 0.7…24 s at 6 x Ir 12.5…600 s at 1.5 x Ir

Thermal memory

20 mn

Short-time protection pick-up adjustment type Isd

Adjustable 9 settings

[Isd] Short-time protection pick-up adjustment range

1.5...10 x Ir

Short-time protection delay adjustment type tsd

Adjustable

[tsd] Short-time protection delay adjustment range

0…0.4 s I²t=off 0.1…0.4 s I²t=on

Instantaneous protection pick-up adjustment type Ii

Adjustable 9 settings

[Ii] instantaneous protection pick-up adjustment range

2...15 x In Off

Ground-fault protection pick-up adjustment type Ig

Adjustable 9 settings

[Ig] ground-fault protection pick-up adjustment range

0.2...1 x In for 400 A < In < 1250 A 0.3...1 x In for In <= 400 A 500...1200 A for In >= 1250 A

Ground-fault protection time delay adjustment type tg

Adjustable

[tg] ground-fault protection time delay adjustment range

0…0.4 s I²t=off 0.1…0.4 s I²t=on

earth-leakage protection

Without

Zone selective interlocking ZSI

With

Local signalling

3 LEDs (red) for electrical fault 1 LED (red) for internal error

Display type

Digital display

Type of measurement

Energy meter

communication of data

Measurement readout Protection and alarm settings

Ambient air temperature for operation

-25…70 °C

Ambient air temperature for storage

-40…85 °C

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

6.8 cm

Package 1 Width

8.0 cm

Package 1 Length

21.5 cm

Package 1 Weight

347.0 g

Warranty

18 months

Document Links

Catalogue page

Datasheet