Information

This Acti9 iPRD20 surge arrester protects 3P+N installations. It allows quick replacement of damaged cartridges. This Type 2 device is recommended for medium risk level and incoming panel board. It can be turned over to allow the phase/neutral/earth cables to enter through either the top or the bottom. The associated circuit breaker Isc breaking capacity can go up to 50kA. This Acti9 iPRD20 is compatible with TT and TN-S earthing system. The Imax rated discharge current is 20kA. The In nominal discharge current is 5kA. The Uc maximum continuous operating voltage in common mode is 260VAC between neutral and earth, and 350VAC between phase and earth. The Up Voltage protection level in differential mode (between phase and neutral) is 1.1kV. The Up Voltage protection level in common mode (between neutral and earth) is 1.4kV. The Ue operating voltage is 230VAC or 400VAC +/- 10%. The operating frequency is 50Hz or 60Hz. The dimensions are (W) 72mm x (H) 85mm x (D) 69mm. The width in 9mm pitches is 8. The weight is 450g. The degree of protection is IP20 and IP40 in modular enclosure. The operating temperature is -25°C to +60°C. The storage temperature is -40°C to +85°C. This product is compliant with EN 61643-11 and IEC 61643-11 standard.

Technical Specifications

range of product

Acti9

Product name

Acti9 iPRD

Product or component type

Surge arrester with pluggable cartridge

Device short name

iPRD20

Device application

Distribution

Standards

EN 61643-11:2012 IEC 61643-11:2011

product certifications

CE

Quality labels

NF KEMA-KEUR

Poles description

3P + N

Remote signalling

Without

Surge arrester type

Electrical distribution network

Earthing system

TT TN-S

Surge arrester class type

Type 2

Surge arrester technology

MOV + GDT

[Ue] rated operational voltage

230/400 V AC (+/- 10 %) at 50/60 Hz

[In] nominal discharge current

Common mode: 5 kA (L/PE) Common mode: 5 kA (N/PE) Differential mode: 5 kA (L/N)

[Imax] maximum discharge current

Common mode: 20 kA L/PE Common mode: 20 kA N/PE Differential mode: 20 kA L/N

[Uc] maximum continuous operating voltage

Common mode: 260 V N/PE Common mode: 350 V L/PE Differential mode: 350 V L/N

Maximum [Up] voltage protection level

Differential mode <1.1 kV type 2 L/N Common mode <1.4 kV type 2 N/PE

[Ut] temporary overvoltage

337 V L/N 5 s withstand 1200 V N/PE 200 ms safe failure mode 442 V L/PE 5 s withstand 1453 V L/PE 200 ms safe failure mode

Disconnector device type

Associated circuit breaker IC60N 20 A curve C - Icu 10 kA Associated circuit breaker iC60H 20 A curve C - Icu 15 kA Associated circuit breaker iC60L 20 A curve C - Icu 25 kA Associated circuit breaker NG125H 20 A curve C - Icu 36 kA Associated circuit breaker NG125L 20 A curve C - Icu 50 kA Associated fuse gG 40 A - Icu 15 kA Associated fuse gG 80 A - Icu 50 kA

Mounting mode

Clip-on (DIN rail)

9 mm pitches

8

height

85 mm

Width

72 mm

Depth

69 mm

Net weight

0.414 kg

Colour

White (RAL 9003)

[Ipe] Ground residual current

0.6 mA 0.003 mA

Connections - terminals

Tunnel type terminal (downside) 2.5…35 mm² Tunnel type terminal (upside) 2.5…35 mm²

Tightening torque

2.5 N.m

IK degree of protection

IK03 conforming to IEC 62262

Relative humidity

5…95 %

Operating altitude

2000 m

ambient air temperature for operation

-25…60 °C

Ambient air temperature for storage

-40…85 °C

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

7.5 cm

Package 1 Width

8 cm

Package 1 Length

9 cm

Package 1 Weight

441 g

Unit Type of Package 2

BB1

Number of Units in Package 2

3

Package 2 Height

8 cm

Package 2 Width

9.5 cm

Package 2 Length

27.5 cm

Package 2 Weight

1.384 kg

Unit Type of Package 3

S03

Number of Units in Package 3

27

Package 3 Height

30 cm

Package 3 Width

30 cm

Package 3 Length

40 cm

Package 3 Weight

12.982 kg

Warranty

18 months

Document Links

Datasheet