Trade Price
£256.64
Per
1
Unit
EA
Pack Quantity
1
This is a straight length for Canalis KBB busbar trunking. Canalis KBB is designed for lighting and power socket distribution. The rated operational current is 25A at 35°C. The rated operational voltage is from 230VAC to 400VAC 50/60Hz. This straight length is made of 3 tap-off outlets maximum spaced every meter on the main circuit (front), and 2 tap-off outlets maximum on the adjacent circuit (rear). It embeds 2 independent electrical circuits with 3L+N+PE polarity. This feed unit is delivered with an optional remote control circuit made of 2 conductors, and is able to transport and distribute DALI protocol for lighting management. It provides IP55 protection conforming to IEC 60529 standard, which guarantees trunking protection against splashes and dust. It provides IK06 protection conforming to IEC 62262 standard against external mechanical impacts. The length is 3m, and the section is 46mm x 46mm. Sold in lots of 6 units. It is made off RAL 9003 white lacquered sheet steel. Canalis KBB is compliant with IEC/EN 61439-6 standard. It is non flame propagating as per the recommendations of IEC 60332-3 standard. All the insulating and plastic materials are halogen free and have enhanced fire withstand capabilities (IEC 60695-2).
Range of product
Canalis
Device short name
KBB
Product or component type
Busbar trunking
Busbar description
Straight length
Device application
Power socket distribution Lighting
[Ie] rated operational current
25 A at 35 °C
[Ue] rated operational voltage
230...400 V
Network frequency
50/60 Hz
busbar trunking polarity
3L + N + PE
Number of circuits
2
Number of tap-off outlets
5
Control type
Communicating
Mounting mode
By screws
[Uimp] rated impulse withstand voltage
4 kV
[Ui] rated insulation voltage
690 V
[Icw] rated short-time withstand current
0.44 kA
[Ipk] rated peak withstand current
4.4 kA
Thermal stress limit
195 kA².s
Maximum radiated magnetic field
2 pT
THDI
0…15 % 25 A 15…33 % 20 A 33…100 % 16 A
Maximum voltage drop
<0.72 V with power factor = 1 at 50 Hz with 1A for 100 m long <0.67 V with power factor = 0.9 at 50 Hz with 1A for 100 m long <0.61 V with power factor = 0.8 at 50 Hz with 1A for 100 m long <0.55 V with power factor = 0.7 at 50 Hz with 1A for 100 m long
standards
EN/IEC 61439-6 EN/IEC 61439-1
Width
30 mm
height
46 mm
Length
3 m
Colour
White (RAL 9003)
Net weight
4.8 kg
IP degree of protection
IP55 conforming to EN/IEC 60529
IK degree of protection
IK06 conforming to EN/IEC 62262
Ambient air temperature for operation
0…35 °C (100 % of In) 35…40 °C (96 % of In) 40…45 °C (93 % of In) 45…50 °C (89 % of In) 50…55 °C (85 % of In)
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
6.000 cm
Package 1 Width
5.100 cm
Package 1 Length
310.000 cm
Package 1 Weight
5.000 kg
Unit Type of Package 2
BB1
Number of Units in Package 2
6
Package 2 Height
13.000 cm
Package 2 Width
16.000 cm
Package 2 Length
315.000 cm
Package 2 Weight
32.000 kg
Unit Type of Package 3
PAL
Number of Units in Package 3
72
Package 3 Height
51.000 cm
Package 3 Width
64.000 cm
Package 3 Length
320.000 cm
Package 3 Weight
393.000 kg
Warranty
18 months