KNB16CM2

TAPOFF UNIT 16A LNPE

Trade Price

£102.87

Per

1

Unit

EA

Pack Quantity

1

KNB16CM2

Technical Specifications

Range of product

Canalis

Range compatibility

Canalis (KN) busbar trunking

Product or component type

Tap-off unit

busbar trunking compatibility

Canalis KN busbar trunkingplug-in

[Ie] rated operational current

16 A

Protection type

Circuit breaker: iC60N

Mounting mode

Plug-in with phase selection

Tap-off unit polarity

L+N+PE

Colour

White (RAL 9001)

Device application

Low power distribution

Provided equipment

1 circuit-breaker included cable clamp

[Ue] rated operational voltage

230...500 V depending on protective device

[Uimp] rated impulse withstand voltage

4.6 kV

[Ui] rated insulation voltage

400 V depending on protective device 500 V depending on protective device

Network frequency

50/60 Hz

Electrical connection

Cable clamp terminal 4 mm² flexible Cable clamp terminal 6 mm² rigid

door/cover opening side

Front

Tap-off unit disconnection mode

By drawing out

Standards

IEC 61439-6 IEC 61439-1

Width

79 mm

Depth

70 mm

height

172 mm

Net weight

0.34 kg

Earthing system

TT TN-S

IP degree of protection

IP41 conforming to IEC 60529

IK degree of protection

IK08 conforming to IEC 62262

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

8.400 cm

Package 1 Width

7.400 cm

Package 1 Length

13.500 cm

Package 1 Weight

340.000 g

Unit Type of Package 2

BB1

Number of Units in Package 2

30

Package 2 Height

15.800 cm

Package 2 Width

28.500 cm

Package 2 Length

43.500 cm

Package 2 Weight

10.615 kg

Unit Type of Package 3

P06

Number of Units in Package 3

60

Package 3 Height

46.500 cm

Package 3 Width

80.000 cm

Package 3 Length

60.000 cm

Package 3 Weight

30.000 kg

Warranty

18 months

Document Links

Catalogue page

Datasheet