Trade Price
£47.18
Per
1
Unit
EA
Pack Quantity
1
Range of product
Canalis
Range compatibility
Canalis (KN) busbar trunking
Product or component type
Tap-off unit
busbar trunking compatibility
Canalis KN busbar trunkingplug-in
[Ie] rated operational current
16 A at 35 °C
protection type
fuse isolator: BS88 fuse, size A1 conforming to BS
Provided equipment
fuse to be ordered separately cable clamp
Mounting mode
Plug-in with phase selection
Tap-off unit polarity
L+N+PE
Colour
White (RAL 9001)
Device application
Low power distribution
[Ue] rated operational voltage
230...500 V depending on protective device
[Uimp] rated impulse withstand voltage
4.6 kV
[Ui] rated insulation voltage
500 V depending on protective device
Network frequency
50/60 Hz
Electrical connection
Cable clamp terminal 4 mm² flexible Cable clamp terminal 6 mm² rigid
door/cover opening side
Front
Tap-off unit disconnection mode
By drawing out
Standards
IEC 61439-1 IEC 61439-6
Width
72 mm
Depth
22 mm
height
172 mm
Net weight
0.18 kg
IP degree of protection
IP55 conforming to IEC 60529
IK degree of protection
IK08 conforming to IEC 62262
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
7.5 cm
Package 1 Width
5 cm
Package 1 Length
13.5 cm
Package 1 Weight
275 g
Unit Type of Package 2
BB1
Number of Units in Package 2
50
Package 2 Height
15.8 cm
Package 2 Width
28.5 cm
Package 2 Length
43.5 cm
Package 2 Weight
14.165 kg
Unit Type of Package 3
P06
Number of Units in Package 3
50
Package 3 Height
44 cm
Package 3 Width
80 cm
Package 3 Length
60 cm
Package 3 Weight
16 kg
Warranty
18 months