3363100

SK AIR/WATER HEAT EXCHANGER 500W REPLACES 3214100

Trade Price

£685.40

Per

1

Unit

EACH

Pack Quantity

1

3363100
3363100
3363100
3363100

Information

Output classes 375 – 5,000 W. For use in tough environments. Convenient mounting options and flexible water connection options. External mounting or full internal mounting possible. For use in harsh environments and temperature ranges up to +70 °C. User-friendly assembly plus flexible water connection options. External mounting or full internal mounting are supported. SK Air/water heat exchanger, wall-mounted, 0.5 kW, 230 V, 1~, 50/60 Hz, basic controller, water-carrying parts: copper/brass, WHD: 280 x 550 x 120 mm

Technical Specifications

Article number:

SK 3363.100

Design

Water-carrying parts, copper/brass (Cu/CuZn)

Colour

RAL 7035

Supply includes

Fully wired ready for connection

Drilling template

Sealing and assembly parts

Total cooling output

L 35 W 10 at 400 l/h: 0.5 kW

Rated operating voltage

230 V, 1~, 50 Hz/60 Hz

Power consumption Pel

At 50 Hz: 37 W

At 60 Hz: 38 W

Rated current max.

At 50 Hz: 0.18 A

At 60 Hz: 0.18 A

Permissible operating pressure (p. max.)

1 ‐ 10 bar

Type of electrical connection

Plug-in terminal strip

Duty cycle

100 %

Cooling medium

Water (see Internet for specifications)

Water inlet temperature

1 °C...30 °C

Water connections

½" connector sleeve

Temperature control

Basic controller (factory setting +35 °C)

Operating temperature range

1 °C...70 °C

Note

Integral non-return valve for version with e-Comfort controller

Dimensions

Width: 280 mm

Height: 550 mm

Depth: 120 mm

Pre-fuse

Miniature circuit-breaker/fuse: 4 A

Setting range

20 °C...55 °C

Protection category to IEC 60 529

IP 55

Protection category NEMA

UL Type 1

Packs of

1 pc(s).

Weight/pack

8 kg

Customs tariff number

84195080

EAN

4028177495630

ETIM 7.0

EC002515

ECLASS 8.0

27180712

Document Links

Catalogue page

Datasheet