DILA-40(110V50/60HZ)

Relay, 4N/O, contactor type

Trade Price

£41.71

Per

1

Unit

EACH

Pack Quantity

1

DILA-40(110V50/60HZ)
DILA-40(110V50/60HZ)
DILA-40(110V50/60HZ)
DILA-40(110V50/60HZ)

Information

Eaton Moeller® series DILA Contactor relay, 110 V 50/60 Hz, 4 N/O, Screw terminals, AC operation

Technical Specifications

Product Length/Depth

75 mm

Product Height

68 mm

Product Width

45 mm

Product Weight

0.24 kg

Compliances

CE Marked

Certifications

UL 508

CSA Std. C22.2 No. 14-05

IEC 60947-4-1

EN 60947-4-1

VDE

UL Category Control No.: NKCR

CE

CSA

UL File No.: E29184

CSA File No.: 012528

IEC/EN 60947-4-1

CSA Class No.: 3211-03

EN 60947-5-1

IEC/EN 60947

UL

VDE 0660

CSA-C22.2 No. 14-05

Features

Positive operating contacts to EN 60947-5-1 appendix L, including auxiliary contact module

Fitted with:

Positive operation contacts

Application

Contactor relays

Degree of protection

IP20

Shock resistance

7 g, N/O auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms

5 g, N/C auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms

Lifespan, mechanical

20,000,000 Operations (AC operated)

Mounting method

DIN rail

Operating frequency

9000 Operations/h

Overvoltage category

III

Pollution degree

3

Product category

DILA relays

Protection

Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)

Rated impulse withstand voltage (Uimp)

6000 V AC

Voltage type

AC

Ambient operating temperature - min

-25 °C

Ambient operating temperature - max

60 °C

Ambient operating temperature (enclosed) - min

25 °C

Ambient operating temperature (enclosed) - max

40 °C

Ambient storage temperature - min

40 °C

Ambient storage temperature - max

80 °C

Climatic proofing

Damp heat, cyclic, to IEC 60068-2-30

Damp heat, constant, to IEC 60068-2-78

Terminal capacity (flexible with ferrule)

1 x (0.75 - 2.5) mm², Screw terminals

2 x (0.75 - 2.5) mm², Screw terminals

Terminal capacity (solid)

2 x (0.75 - 2.5) mm², Screw terminals

1 x (0.75 - 4) mm², Screw terminals

Terminal capacity (solid/stranded AWG)

18 - 14, Screw terminals

Stripping length (main cable)

10 mm

Screw size

M3.5, Terminal screw

Screwdriver size

2, Terminal screw, Pozidriv screwdriver

0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver

Tightening torque

1.2 Nm, Screw terminals

Rated operational current (Ie)

6 A at 60 V, DC L/R <= 15 ms (with 1 contact in series)

10 A at 60 V, DC L/R <= 15 ms (with 2 contacts in series)

1 A at 220 V, DC L/R <= 15 ms (with 1 contact in series)

5 A at 220 V, DC L/R <= 15 ms (with 3 contacts in series)

2 A at 110 V, DC L/R <= 50 ms (with 3 contacts in series)

1 A at 220 V, DC L/R <= 50 ms (with 3 contacts in series)

3 A at 110 V, DC L/R <= 15 ms (with 1 contact in series)

10 A at 24 V, DC L/R <= 15 ms (with 1 contact in series)

4 A at 24 V, DC L/R <= 50 ms (with 3 contacts in series)

4 A at 60 V, DC L/R <= 50 ms (with 3 contacts in series)

6 A at 110 V, DC L/R <= 15 ms (with 3 contacts in series)

16 A

Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V

4 A

Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V

4 A

Rated operational current (Ie) at AC-15, 500 V

1.5 A

Rated insulation voltage (Ui)

690 V

Rated operational voltage (Ue) at AC - max

690 V

Short-circuit protection rating without welding

10 A gG/gL, 500 V, Max. Fuse, Contacts

Safe isolation

400 V AC, Between auxiliary contacts, According to EN 61140

400 V AC, Between coil and auxiliary contacts, According to EN 61140

Switching capacity (auxiliary contacts, general use)

1 A, 250 V DC, (UL/CSA)

15 A, 600 V AC, (UL/CSA)

Switching capacity (auxiliary contacts, pilot duty)

A600, AC operated (UL/CSA)

P300, DC operated (UL/CSA)

Duty factor

100 %

Pick-up voltage

0.8 - 1.1 V AC x Uc (voltage tolerance - dual frequency coil 50/60 Hz)

Power consumption, pick-up, 60 Hz

27 VA, AC, Dual-frequency coil at 60 Hz

25 VA, AC, Dual-frequency coil at 60 Hz

Rated control supply voltage (Us) at AC, 50 Hz - min

110 V

Rated control supply voltage (Us) at AC, 50 Hz - max

110 V

Rated control supply voltage (Us) at AC, 60 Hz - min

110 V

Rated control supply voltage (Us) at AC, 60 Hz - max

110 V

Rated control supply voltage (Us) at DC - max

0 V

Switching time (AC operated, make contacts, closing delay) - min

15 ms

Switching time (AC operated, make contacts, closing delay) - max

21 ms

Switching time (AC operated, make contacts, opening delay) - min

9 ms

Switching time (AC operated, make contacts, opening delay) - max

18 ms

Connection

Screw terminals

Connection to SmartWire-DT

No

Code number

40D

Control circuit reliability

λ < 5 x 10-7 (1 failure at 2,000,000 operations for Uₑ = 24 V DC, Umin = 17 V, Imin = 5.4 mA)

Number of auxiliary contacts (change-over contacts)

0

Number of contacts (normally closed contacts)

0

Number of contacts (normally open contacts)

4

Number of auxiliary contacts (normally open contacts)

4

Equipment heat dissipation, current-dependent Pvid

0 W

Heat dissipation capacity Pdiss

0 W

Heat dissipation per pole, current-dependent Pvid

0.5 W

Rated operational current for specified heat dissipation (In)

15.5 A

Static heat dissipation, non-current-dependent Pvs

1.4 W

10.2.2 Corrosion resistance

Meets the product standard's requirements.

10.2.3.1 Verification of thermal stability of enclosures

Meets the product standard's requirements.

10.2.3.2 Verification of resistance of insulating materials to normal heat

Meets the product standard's requirements.

10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects

Meets the product standard's requirements.

10.2.4 Resistance to ultra-violet (UV) radiation

Meets the product standard's requirements.

10.2.5 Lifting

Does not apply, since the entire switchgear needs to be evaluated.

10.2.6 Mechanical impact

Does not apply, since the entire switchgear needs to be evaluated.

10.2.7 Inscriptions

Meets the product standard's requirements.

10.3 Degree of protection of assemblies

Does not apply, since the entire switchgear needs to be evaluated.

10.4 Clearances and creepage distances

Meets the product standard's requirements.

10.5 Protection against electric shock

Does not apply, since the entire switchgear needs to be evaluated.

10.6 Incorporation of switching devices and components

Does not apply, since the entire switchgear needs to be evaluated.

10.7 Internal electrical circuits and connections

Is the panel builder's responsibility.

10.8 Connections for external conductors

Is the panel builder's responsibility.

10.9.2 Power-frequency electric strength

Is the panel builder's responsibility.

10.9.3 Impulse withstand voltage

Is the panel builder's responsibility.

10.9.4 Testing of enclosures made of insulating material

Is the panel builder's responsibility.

10.10 Temperature rise

The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.

10.11 Short-circuit rating

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.12 Electromagnetic compatibility

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.13 Mechanical function

The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Document Links

Datasheet