Trade Price
£53.97
Per
1
Unit
EACH
Pack Quantity
1
Eaton Moeller series xEffect - FAZ MCB. FAZ, 2-pole, tripping characteristic: B, rated current In: 10 A
Product Length/Depth
80 mm
Product Height
75.5 mm
Product Width
36 mm
Product Weight
0.222 kg
Compliances
UL CSA09 (with supplementary protector only)
RoHS conform
Certifications
IEC/EN 60898
CSA (Class No. 3215-30)
CE marking
UL (File No. E177451)
IEC/EN 60947-2
UL 1077
CSA (File No. 204453)
UL (Category Control Number QVNU2, QVNU8)
North America (UL recognized, CSA certified)
CSA-C22.2 No. 235
EN45545-2
IEC 61373
Rated operational current for specified heat dissipation (In)
10 A
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Voltage rating (IEC/EN 60898-1)
415 VAC
10.4 Clearances and creepage distances
Meets the product standard's requirements.
Rated short-circuit breaking capacity (EN 60898) at 230 V
10 kA
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Mounting Method
Top-hat rail IEC/EN 60715
Current limiting class
3
Rated short-circuit breaking capacity (EN 60898) at 400 V
10 kA
Amperage Rating
10 A
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
Terminal capacity of screw terminals for main cable
10 mm² (2x)
Frequency rating - max
60 Hz
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.8 Connections for external conductors
Is the panel builder's responsibility.
Rated short-circuit breaking capacity (IEC 60947-2) at 400 V
15 kA
Number of poles (total)
2
Terminal protection
Finger and hand touch safe, DGUV VS3, EN 50274
Rated short-circuit breaking capacity (IEC 60947-2) at 230 V
15 kA
Special features
Ambient temperature hint: a 1 °C increase results in a 0.5% linear reduction of current carrying capacity
Ambient operating temperature - max
75 °C
Heat dissipation per pole, current-dependent
0 W
Built-in depth
70.5 mm
Rated switching capacity (IEC/EN 60898-1)
10 kA
Features
Additional equipment possible
Lifespan, electrical
10000 operations
Rated switching capacity (IEC/EN 60947-2) at max voltage rating
10 kA
Connectable conductor cross section (solid-core) - min
1 mm²
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
Number of poles
Two-pole
Ambient operating temperature - min
-25 °C
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
Selectivity class
3
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
Terminal capacity (control cable)
25 mm² (1x)
Used with
FAZ
Miniature circuit breaker
Mounting position
As required
Equipment heat dissipation, current-dependent
3.9 W
Tripping characteristic
B
Frequency rating - min
50 Hz
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Static heat dissipation, non-current-dependent
0 W
Application
Branch circuits, not as BCPD
Switchgear for industrial and advanced commercial applications
xEffect - Switchgear for industrial and advanced commercial applications
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
Voltage type
AC
Number of poles (protected)
2
Frame
45 mm
Terminals (top and bottom)
Twin-purpose terminals
Heat dissipation capacity
0 W
Release characteristic
B
Width in number of modular spacings
2
Busbar material thickness
0.8 mm - 2 mm
Power loss
3.6 W
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
Enclosure width
80 mm
Voltage rating
240 V AC / 415 V AC
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
Connectable conductor cross section (solid-core) - max
25 mm²
Degree of protection
IP40 (when fitted)
IP20 (IEC)
UL/CSA Type: -
IP20
Overvoltage category
III
Pollution degree
2
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
Connectable conductor cross section (multi-wired) - min
1 mm²
Rated impulse withstand voltage (Uimp)
4 kV
Operational voltage (IEC/EN 60947-2) - max
440 VAC
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Voltage rating at DC
60 V DC (per pole)
Admissible back-up fuse - max
125 A gL/gG
Voltage rating (UL)
480Y/277 V
Rated switching capacity (IEC/EN 60947-2)
15 kA
Voltage rating (UL CSA 13)
480 Y/277 V AC; 96 V DC
Connectable conductor cross section (multi-wired) - max
25 mm²
Mounting width per pole
17.5 mm
Type
FAZ
Miniature circuit breaker
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.7 Inscriptions
Meets the product standard's requirements.
Operational switching capacity
7.5 kA
Breaking capacity
10 kA (UL1077)
Direction of incoming supply
As required
Rated operational voltage (Ue) - max
400 V
Rated service short-circuit breaking capacity (IEC/EN 60898-1)
7.5 kA
Mounting width
17.5 mm
Rated service short-circuit breaking capacity (IEC/EN 60947-2)
7.5 kA
Rated insulation voltage (Ui)
440 V
Datasheet