Eaton Moeller series xEffect - FAZ-NA, FAZ-RT MCB. FAZ-RT, 2-pole, tripping characteristic: D, rated current In: 8 A
Product Length/Depth
105 mm
Product Height
75.5 mm
Product Width
35.4 mm
Product Weight
0.247 kg
Compliances
RoHS conform
Certifications
CE marking
IEC 60947-2
CSA (Class No. 1432-01)
UL (Category Control Number DIVQ)
UL 489, CSA C22.2 No. 5
IEC/EN 60947-2
CSA (File No. 204453)
UL (File No. E235139)
Specially designed for North America, suitable as BCPD
North America (UL listed, CSA certified)
CSA-C22.2 No. 5-09
UL 489
EN45545-2
IEC 61373
Rated operational current for specified heat dissipation (In)
8 A
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
Rated short-circuit breaking capacity (EN 60898) at 230 V
0 kA
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Mounting Method
Top-hat rail IEC/EN 60715
Current limiting class
3
Rated short-circuit breaking capacity (EN 60898) at 400 V
0 kA
Amperage Rating
8 A
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
Frequency rating - max
60 Hz
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.8 Connections for external conductors
Is the panel builder's responsibility.
Rated short-circuit breaking capacity (IEC 60947-2) at 400 V
15 kA
Number of poles (total)
2
Terminal protection
Finger and hand touch safe, DGUV VS3, EN 50274
Rated short-circuit breaking capacity (IEC 60947-2) at 230 V
15 kA
Special features
Ambient temperature hint: a 1 °C increase results in a 0.5% linear reduction of current carrying capacity
Ambient operating temperature - max
75 °C
Heat dissipation per pole, current-dependent
0 W
Built-in depth
70.5 mm
Features
Additional equipment possible
Lifespan, electrical
20000 operations
Connectable conductor cross section (solid-core) - min
1 mm²
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
Number of poles
Two-pole
Ambient operating temperature - min
-25 °C
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
Selectivity class
3
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
Used with
FAZ-RT
Miniature circuit breaker
Mounting position
As required
Equipment heat dissipation, current-dependent
2.4 W
Tripping characteristic
D
Frequency rating - min
50 Hz
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Static heat dissipation, non-current-dependent
0 W
Application
Feeder circuits, branch circuits
Switchgear for industrial and advanced commercial applications
xEffect - Switchgear for industrial and advanced commercial applications
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
Voltage rating (IEC/EN 60947-2)
415 V
Voltage type
AC
Number of poles (protected)
2
Frame
45 mm
Terminals (top and bottom)
Twin-purpose terminals
Heat dissipation capacity
0 W
Release characteristic
D
Width in number of modular spacings
2
Power loss
2.6 W
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
Enclosure width
105 mm
Voltage rating
277 V AC / 480 V AC
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
Connectable conductor cross section (solid-core) - max
25 mm²
Degree of protection
UL/CSA Type: -
IP20
IP40 (when fitted)
IP20 (IEC)
Overvoltage category
III
Pollution degree
2
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
Connectable conductor cross section (multi-wired) - min
1 mm²
Rated impulse withstand voltage (Uimp)
4 kV
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Voltage rating at DC
60 V DC
Functions
Current limiting circuit breaker
Tightening torque
UL: 2.8 Nm (25 lb-in) for AWG 10 - AWG 8
UL: 4 Nm (36 lb-in) for AWG 6
Max. 2.4 Nm
UL: 2.4 Nm (21 lb-in) for AWG 18 - AWG 12
Voltage rating (UL)
480Y/277 V
Rated switching capacity (IEC/EN 60947-2)
15 kA
Connectable conductor cross section (multi-wired) - max
25 mm²
Mounting width per pole
17.7 mm
Type
FAZ-RT
Miniature circuit breaker
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.7 Inscriptions
Meets the product standard's requirements.
Direction of incoming supply
As required
Rated operational voltage (Ue) - max
415 V
Mounting width
17.7 mm
Rated insulation voltage (Ui)
440 V