DILM32-XTED11-10(RAC130)

Timer module,0.5-10s,off-delay

Trade Price

£85.86

Per

1

Unit

EACH

Pack Quantity

1

DILM32-XTED11-10(RAC130)

Information

Eaton Moeller® series DILM Timer module, 100-130VAC, 0.5-10s, off-delayed

Technical Specifications

Product Length/Depth

86 mm

Product Height

38 mm

Product Width

45 mm

Product Weight

0.073 kg

Certifications

CSA-C22.2 No. 14-05

CSA

CSA Class No.: 3211-03

UL 508

IEC/EN 60947-4-1

UL

UL Category Control No.: NKCR

VDE 0660

CE

CSA File No.: 012528

DIN EN 61812

IEC/EN 60947

UL File No.: E29184

Catalog Notes

Cannot be combined with top mounting auxiliary contacts

Fitted with:

Suppressor circuits

Operating mode

Electronic

Delay time

200 ms, Off-delayed

50 ms, On-delayed

Lifespan, mechanical

3,000,000 Operations (AC operated)

3,000,000 Operations (DC operated)

Operating frequency

3600 Operations/h

360 mechanical Operations/h

Overvoltage category

III

Pollution degree

3

Product category

Accessories

Protection

Finger and back-of-hand proof, Protection against direct contact when actuated from front

Rated impulse withstand voltage (Uimp)

4000 V AC

Recovery time

70 ms (after 100 % time delay)

Mounting position

As required (except suspended)

Shock resistance

6 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms

6 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms

Ambient operating temperature - min

-25 °F

Ambient operating temperature - max

60 °F

Ambient operating temperature (enclosed) - min

25 °F

Ambient operating temperature (enclosed) - max

40 °F

Ambient storage temperature - min

40 °F

Ambient storage temperature - max

80 °F

Climatic proofing

Damp heat, cyclic, to IEC 60068-2-30

Damp heat, constant, to IEC 60068-2-78

Terminal capacity (flexible with ferrule)

2 x (0.75 - 1.5) mm²

1 x (0.75 - 1.5) mm²

Terminal capacity (solid)

2 x (0.75 - 1.5) mm²

1 x (0.75 - 2.5) mm²

Terminal capacity (solid/stranded AWG)

18 - 14

Screw size

M3.5, Terminal screw, Control circuit cables

Screwdriver size

0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver

2, Terminal screw, Pozidriv screwdriver

Rated operational current (Ie)

0.2 A at 60 V, DC-13 L/R - 300 ms (with 1 contact in series)

0.1 A at 220 V, DC-13 L/R - 300 ms (with 1 contact in series)

0.2 A at 110 V, DC-13 L/R - 50 ms (with 1 contact in series)

0.2 A at 110 V, DC-13 L/R - 300 ms (with 1 contact in series)

3 A at AC-15, 220 V 230 V 240 V

0.1 A at 220 V, DC-13 L/R - 50 ms (with 1 contact in series)

0.2 A at 60 V, DC-13 L/R - 50 ms (with 1 contact in series)

1 A at 24 V, DC-13 L/R - 50 ms (with 1 contact in series)

1 A at 24 V, DC-13 L/R - 300 ms (with 1 contact in series)

Short-circuit current rating (basic rating)

5 kA, SCCR (UL/CSA)

125 A, max. CB, SCCR (UL/CSA)

125 A, max. Fuse, SCCR (UL/CSA)

Short-circuit current rating (high fault at 480 V)

125/70 A, Class J, max. Fuse, SCCR (UL/CSA)

10/65 kA, CB, SCCR (UL/CSA)

10/100 kA, Fuse, SCCR (UL/CSA)

50/32 A, max. CB, SCCR (UL/CSA)

Short-circuit current rating (high fault at 600 V)

125/125 A, Class J, max. Fuse, SCCR (UL/CSA)

10/22 kA, CB, SCCR (UL/CSA)

10/100 kA, Fuse, SCCR (UL/CSA)

50/32 A, max. CB, SCCR (UL/CSA)

Short-circuit protection rating

Max. 4 A gG/gL, fuse, Without welding, Auxiliary and control circuits

Conventional thermal current ith of auxiliary contacts (1-pole, open)

4 A

Switching capacity (auxiliary contacts, general use)

5 A, 240 V AC, (UL/CSA)

5 A, 24 V DC, (UL/CSA)

Switching capacity (auxiliary contacts, pilot duty)

B300, AC operated (UL/CSA)

R300, DC operated (UL/CSA)

Duty factor

100 %

Pick-up voltage

0.7 - 1.2 V DC x Uc

0.85 - 1.1 V AC x Uc

Power consumption (sealing) at DC

1.8 W

Power consumption, sealing, 50 Hz

2 VA, Coil in a cold state and 1.0 x Us

Power consumption, sealing, 60 Hz

2 VA, Coil in a cold state and 1.0 x Us

Rated control supply voltage (Us) at AC, 50 Hz - min

100 V

Rated control supply voltage (Us) at AC, 50 Hz - max

130 V

Rated control supply voltage (Us) at AC, 60 Hz - min

100 V

Rated control supply voltage (Us) at AC, 60 Hz - max

130 V

Number of contacts (change-over contacts)

0

Number of contacts (normally closed contacts)

1

Number of contacts (normally open contacts)

1

Safe isolation

250 V AC, Between coil and auxiliary contacts, According to EN 61140

250 V AC, Between auxiliary contacts, According to EN 61140

Equipment heat dissipation, current-dependent Pvid

0 W

Heat dissipation capacity Pdiss

0 W

10.2.2 Corrosion resistance

Meets the product standard's requirements.

10.2.3.2 Verification of resistance of insulating materials to normal heat

Meets the product standard's requirements.

10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects

Meets the product standard's requirements.

10.2.4 Resistance to ultra-violet (UV) radiation

Meets the product standard's requirements.

10.2.5 Lifting

Does not apply, since the entire switchgear needs to be evaluated.

10.2.6 Mechanical impact

Does not apply, since the entire switchgear needs to be evaluated.

10.2.7 Inscriptions

Meets the product standard's requirements.

10.3 Degree of protection of assemblies

Does not apply, since the entire switchgear needs to be evaluated.

10.4 Clearances and creepage distances

Meets the product standard's requirements.

10.5 Protection against electric shock

Does not apply, since the entire switchgear needs to be evaluated.

10.6 Incorporation of switching devices and components

Does not apply, since the entire switchgear needs to be evaluated.

10.7 Internal electrical circuits and connections

Is the panel builder's responsibility.

10.8 Connections for external conductors

Is the panel builder's responsibility.

10.9.2 Power-frequency electric strength

Is the panel builder's responsibility.

10.9.3 Impulse withstand voltage

Is the panel builder's responsibility.

10.10 Temperature rise

The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.

10.11 Short-circuit rating

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.12 Electromagnetic compatibility

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.13 Mechanical function

The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.