NZMN2-A125-BT

MCCB NZM2 3pole 125A 50kA therm/mag box terminal

Trade Price

£539.56

Per

1

Unit

EACH

Pack Quantity

1

NZMN2-A125-BT

Information

Eaton Moeller series NZM - Molded Case Circuit Breaker. Circuit-breaker, Standard equipment: Box terminal, Switching capacity 400/415 V 50 Hz: Icu 50 kA, In = Iu 125 A

Technical Specifications

Product Length/Depth

149 mm

Product Height

184 mm

Product Width

105 mm

Product Weight

2.724 kg

Compliances

RoHS conform

Certifications

IEC

IEC/EN 60947

Voltage rating

690 V - 690 V

Voltage rating (DC)

750 VDC

Rated impulse withstand voltage (Uimp) at auxiliary contacts

6000 V

Rated impulse withstand voltage (Uimp) at main contacts

8000 V

Rated short-time withstand current (t = 0.3 s)

1.9 kA

Rated short-time withstand current (t = 1 s)

1.9 kA

Amperage Rating

125 A

Instantaneous current setting (Ii) - min

750 A

Instantaneous current setting (Ii) - max

1250 A

Overload current setting (Ir) - min

100 A

Overload current setting (Ir) - max

125 A

Short delay current setting (Isd) - min

0 A

Short delay current setting (Isd) - max

0 A

Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz

85 kA

Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz

50 kA

Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz

35 kA

Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 525 V, 50/60 Hz

25 kA

Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 690 V, 50/60 Hz

5 kA

Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 500 V DC

7.5 kA

Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 750 V DC

7.5 kA

Rated short-circuit making capacity Icm at 240 V, 50/60 Hz

187 kA

Rated short-circuit making capacity Icm at 400/415 V, 50/60 Hz

110 kA

Rated short-circuit making capacity Icm at 440 V, 50/60 Hz

77 kA

Rated short-circuit making capacity Icm at 525 V, 50/60 Hz

55 kA

Rated short-circuit making capacity Icm at 690 V, 50/60 Hz

40 kA

Short-circuit total breaktime

< 10 ms

Electrical connection type of main circuit

Frame clamp

Isolation

300 V AC (between the auxiliary contacts)

500 V AC (between auxiliary contacts and main contacts)

Number of operations per hour - max

120

Handle type

Rocker lever

Utilization category

A (IEC/EN 60947-2)

Overvoltage category

III

Pollution degree

3

Lifespan, electrical

10000 operations at 400 V AC-1

6500 operations at 400 V AC-3

7500 operations at 690 V AC-1

6500 operations at 415 V AC-3

5000 operations at 690 V AC-3

10000 operations at 415 V AC-1

Direction of incoming supply

As required

Mounting Method

Built-in device fixed built-in technique

Fixed

DIN rail (top hat rail) mounting optional

Degree of protection

IP20

IP20 (basic degree of protection, in the operating controls area)

Degree of protection (IP), front side

IP40 (with insulating surround)

IP66 (with door coupling rotary handle)

Degree of protection (terminations)

IP10 (tunnel terminal)

IP00 (terminations, phase isolator and strip terminal)

Protection against direct contact

Finger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110

Shock resistance

20 g (half-sinusoidal shock 20 ms)

Number of auxiliary contacts (change-over contacts)

0

Number of auxiliary contacts (normally closed contacts)

0

Number of auxiliary contacts (normally open contacts)

0

Position of connection for main current circuit

Front side

Climatic proofing

Damp heat, constant, to IEC 60068-2-78

Damp heat, cyclic, to IEC 60068-2-30

Lifespan, mechanical

20000 operations

Document Links