For Powerstar VM160 Panel Boards. Use in conjunction with inter-connection kit. Electronic trip unit (LI) for system protection, with adjustable electronic elements. Requires interconnection kit to connect to main busbars.
Rated permanent current Iu
630 A
Rated voltage
400 V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
55 kA
Overload release current setting
250-630 A
Integrated earth fault protection
No
Type of electrical connection of main circuit
Other
Device construction
Complete device in housing
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
With switched-off indicator
No
With integrated under voltage release
No
Number of poles
4
Position of connection for main current circuit
Other
Type of control element
Toggle
Complete device with protection unit
Yes
Motor drive integrated
No
Motor drive optional
Yes
Degree of protection (IP)
IP40
CE Conformity
Yes
WEEE Symbol
Yes
UKCA Conformity
Yes