LU200/DCB

200A 3P Direct connection Incomer Kit

Trade Price

£136.27

Per

1

Unit

EACH

Pack Quantity

LU200/DCB

Information

• Accessory for Polestar Compact Distribution Boards • To be used in conjunction with C50 & Series 16 Polestar replacement pan assembly kits • Suitable in areas with fire resistant structure as per LU standard 1-091 • NB; Due to its narrow width (335mm) the C50 distribution board is unable to accept the Polestar compact 702 series single mod RCBO • NB; Important, under no circumstances should cable connections be made direct to the phase busbars. A suitable mains incoming device must be fitted to ensure adequate busbar support

Technical Specifications

Mounting method

Other

Number of phases

3

Number of poles main switch

3

Main switch rated current

200 A

Material housing

Steel

Product Standard/s

BS EN 61439-3

Frequency

50 / 60 Hz

CE Conformity

Yes

WEEE Symbol

Yes

UKCA Conformity

Yes

Amperage

200 A

Fault Rating

16

Pole Configuration

3

Operating Voltage

230 / 400 V

Type of Current

AC

Busbar type

Solid coppers

Document Links

Catalogue page

Datasheet