CP414TV

CAST-PRO Smoke + Heat Multisensor c/w Tone Sounder & C-3-9.4 White VAD

Trade Price

£109.60

Per

Unit

Pack Quantity

CP414TV

Information

Multiple functionality in a single device – smoke & heat multisensor fire detection plus a 92db(A) tone Alarm sounder and a C-3-9.4 VAD – detects real fires quickly, reduces false alarms effectively and indicates true alarm conditions decisively. Certified to EN54-3, 5, 7, 17, 23 & 29. Compatible with C-TEC’s ZFP touchscreen-controlled CAST protocol addressable fire panel. MASC™ (Miniature Advanced Smoke Detection Chamber) and AFFIRM™ algorithms provide incredible tolerance to false alarms whilst enhancing the detection of real fire conditions. Drift compensation functionality. Onboard short circuit loop isolator. Includes two 8mm x 2mm ultra-bright red LED indicating strips. Multiple detection modes and different sensitivities for different times of the day. 13.2mA max. alarm current (max vol, VAD on). 590uA typical quiescent current @ 40V DC. Compatible with C-TEC’s CA408 CAST base c/w integrated locking mechanism & ID tag.

Technical Specifications

Approvals/certifications

CPR number 0063-CPR-242190011

Compatibility

Compatible with C-TEC's ZFP CAST Addressable Fire Alarm Systems

Type

Heat & Smoke Fire Detection plus Tone Alarm & White VAD

Sensitivity

8 Detection Modes (default for this device is Mode 7).

Supply wiring

2-wire, polarity sensitive.

Supply/operating voltage

28 to 40V DC.

Quiescent current

590uA @ 40V.

VAD category & coverage

C-3-9.4 (10m2/mA efficiency; 0.5Hz Synchronised).

Indicators

2 LED indicator strips emitting red light when in alarm offering 360º visibility. Optional remote LED.

Connections

Via CA408 base: 1 +Ve IN (analogue switch); 2 +Ve OUT (analogue switch); 3 Remote LED +Ve; 4 0V; 5 0V; 6 Screen; 7 Screen.

Product dimensions (mm)

105mm diameter x 51mm deep (detector only); 105mm diameter x 68mm deep (detector in base).

IP Rating

IP21C

Weight

130g (not in base); 185g (in base).

Operating conditions/temperature

-10ºC to +50ºC. Max relative humidity: 95% (non-condensing)

Notes

Requires a CA408 CAST base. CA408R relay base also available.

Document Links

Datasheet