A cost-effective expansion kit that adds true BS8300 compliant accessible toilet alarm functionality to a Quantec Addressable Call System. Includes a QT607 ceiling pull unit, a QT605S reset point c/w confidence sounder, a Quantec slave overdoor light c/w sounder and an NC949 Accessible Toilet Sticker. Allows people in distress to call for help quickly and easily. Call acknowledgement function provides audible & visual feedback inside the WC that help is on the way (see Operation section below). Staff can ‘Accept’ alarm calls at a Quantec display. Multiple kits can be used on one Quantec system. Includes a free MRSA resistant anti-bacterial pull cord pack (for a limited period only). Backwards compatible. Must be used in conjunction with at least one Quantec Controller.
Mains supply
Power derived from main QT601-2 Quantec Controller (not supplied).
Internal power supply
N/A.
Total output current limited to
N/A.
Quiescent current
Typically 6mA.
Zone current
N/A.
Max battery size and type
An optional standby battery supply (2 x 12V 7Ah VRLA) can be connected at the main QT601-2 Quantec Controller, not supplied.
Alarm current
Less than 30mA (all QT951 devices).
Auxiliary relays
N/A. However optional QT612 Relay Output Devices can be connected to the Quantec network/wiring.
Indicators
QT607 has a red Reassurance LED; QT605S has a red/green Reassurance LED; QT606S has twin red/green Alarm LEDs.
Controls
QT607 Ceiling pull activated by two pull cord bangles. QT605S has a Reset button. Call "Accept" function can be carried out at a Quantec Display (not supplied).
Expansion connections
N/A. However additional call and indicating devices can be connected to the Quantec network/wiring.
Onboard Sounder
Yes (on QT605S and QT606S).
Onboard Infrared Receiver
No.
Product dimensions (mm)
87 W x 87 H x 68 D (QT606S); 87 W x 87 H x 24 D (QT605S). Ceiling pull measures 93mm diameter x 27 D.
Packaging dimensions (mm)
143 W x 96 H x 102 D mm (size of QT951 kit box containing all items).
Construction & finish
Plastic.
IP Rating
IP41 (QT606S); IP40 (QT605S); IP21 (QT607).
Weight
0.30kg.
Operating conditions/temperature
-5ºC to +40ºC. Max relative humidity: 95%.
Notes