BF367

Auxiliary Device Isolator

Trade Price

£29.99

Per

1

Unit

EACH

Pack Quantity

BF367

Information

Allows a +24 VDC output from a fire alarm control panel to be remotely isolated to prevent autodiallers, water sprinklers, rollershutters, etc., from activating. Designed so that if monitoring is used on the +24 VDC output being controlled, a fault condition will show at the fire panel when the device is Isolated. Label includes a white ‘write on’ area allowing installers to add equipment locations. Fits on standard UK 25mm flush or surface mount back boxes.

Technical Specifications

Activation current

10mA @ 27.6 VDC required to illuminate the amber Isolated LED

Indicators

Isolated LED.

Connections

OV; SW In; SW Out.

Product dimensions (mm)

85 W x 85 H x D 19mm.

Construction & finish

White PVC plate; Grey label; Silver plated brass switch material.

IP Rating

IP40.

Weight

TBC.

Operating conditions/temperature

-10ºC to +60ºC.

Notes

Switching Resistive load 3A @ 30V DC; Switching Inductive load 1.5A @ 30V DC; Non-switching current rating 5A Absolute Max.

Document Links

Catalogue page

Datasheet