Trade Price
£244.76
Per
1
Unit
EACH
Pack Quantity
Can be used to repeat the functions of a master CFP standard or AlarmSense 2-8 zone fire panel at remote parts of site (e.g. all potential fire service entrances). Up to 8 repeaters per CFP master. Includes its own Mains power supply that requires its own standby battery supply. Provides the user with access to all AL1 and AL2 functions. Master/Repeater communication achieved using CFP761 network driver cards (one CFP761 is supplied with the Repeater, an additional CF761 card is required at the master CFP). Communicates over screened two-wire fire resistant cable. Total repeater network cable length should not exceed 1KM. Attractive flush or surface mountable plastic lid and enclosure – no bezel required.
Compatibility
Compatible with C-TEC's CFP Standard and CFP AlarmSense panels. (Legacy CFP Economy panels cannot be extended with this product).
Mains supply
230V 50/60Hz.
Internal power supply
19V-28.5V (27V nominal).
Max battery size and type
2 x 12V 2.1Ah VRLA connected in series for 72 hour standby. 2 x 12V 1.2Ah for 24 hours.
Max. network cable length
1KM.
Product dimensions (mm)
380 W x 235 H x D 96mm (hole required for flush mounting = 367 W x 220 H x 75 D mm. No bezel required).
Construction & finish
Plastic lid and base; RAL7035 textured
IP Rating
IP30.
Weight
1.75kg (without batteries)
Operating conditions/temperature
-5ºC to +40ºC. Max relative humidity: 95%.
Datasheet