Provides ‘W-2.75-9’ rated light distribution when wall mounted (min. 0.4 lux over a 2.75 x 9m cuboid area). Can also be used as a W-4-4 VAD. Superb sound intelligibility. Choose from two evacuation voice messages and four evacuation alarm tones (your selected evacuation message will be preceded by the selected tone). Three selectable VAD flash rates (0.5Hz, 1Hz, OFF) Alarm Current at 30Vdc = 17mA (0.5Hz) or 24mA (1Hz) Alarm Current at 18Vdc = 18.5mA (0.5Hz) or 30mA (1Hz) IP55C rated (weatherproof). Manufactured in the UK by C-TEC.
Protocol/compatibility
Compatible with C-TEC's CFP, FP, MFP and EP203 conventional fire alarm panels and virtually all other makes (testing on third-party panels is recommended before use)
Application/operation
Designed to be wall mounted. Can be used in covered outdoor areas.
VAD category & coverage
W-2.75-9 rated light distribution (min. 0.4 lux over a 2.7.5m x 9m cuboid area). Can also be used as a W-4-4 VAD.
Flash rate & colour
0.5Hz; 1Hz or OFF / White.
Supply/operating voltage
18 to 30V DC.
Nominal SPL (Sound Pressure Level)
88dB(A) @ 1m.
Alarm current
At 30Vdc: 17mA (0.5Hz) or 24mA (1Hz); At 18Vdc: 18.5mA (0.5Hz) or 30mA (1Hz)
Product dimensions (mm)
114mm diameter x 132mm deep.
IP Rating
IP55C (Weatherproof).
Weight
315g.
Operating conditions/temperature
-10ºC to +55ºC. Max. 95% RH (Non-condensing).
Wall Mounted
Lux level in area requiring coverage
Direct Viewing
000-101 lux
14.30m H x 46.80m W
101-200 lux
12.10m H x 39.60m W
201-300 lux
8.80m H x 28.80m W
301-400 lux
6.32m H x 20.70m W
401-500 lux
4.95m H x 14.40m W
501-600 lux
3.57m H x 11.7m W
601-700 lux
2.75m H x 9.0m W
701-800 lux
1.90m H x 6.3W