Trade Price
£496.05
Per
1
Unit
EACH
Pack Quantity
Can be used to repeat the functions of an XFP Main panel at remote parts of a site (e.g. all potential fire service entrances). Offers all of the functions and controls of an XFP Main panel (access levels 1, 2 and 3). Includes an on-board fault relay. Requires its own dedicated Mains power and battery back-up supply. A maximum of eight XFP Repeaters can be connected to one non-networked XFP Main panel. Communication between the XFP Main panel and Repeater requires an AFP711 network driver card (fitted as standard in all XFP510-32s, available as an optional extra on Main XFP 32 Zone panels). Repeater network is non-redundant and wired in 1.5 mm2 two-core screened fire resistant cable. Network length must not exceed 500 metres.
Protocol/compatibility
Compatible with C-TEC's XFP CAST, Apollo XP95/Discovery and Hochiki ESP main panels.
Mains supply
230V 50/60Hz.
Mains rated current
680mA maximum.
Internal power supply
27Vdc nominal.
Total output current limited to
3A @ 230Vac (Imax.A 250mA; Imin. 70mA).
Quiescent current
TBC.
Max battery size and type
2 x 12V 7Ah VRLA connected in series.
Auxiliary relays
Fault (Failsafe; Capable of switching 1A @ 30V DC; Must not be used for switching Mains voltages).
PC connection
None.
Indicators
2 line x 40 character backlit display; 32 Zonal LEDs, General Fire; Energised; Pre-Alarm; Remote Output Activated; Remote Output Disabled; Accessed; Disablement; Test; Silenced; General Fault; Syst
Expansion connections
On board AFP711 network driver card facilitates the connection of additional XFP Repeaters.
Product dimensions (mm)
410 W x 250 H x 80 D mm (base); 439 W x 274 H x 7 D mm (lid). Hole required for semi-flush mounting = 412 W x 255 H x 50 D mm (requires XFP385 bezel).
Construction & finish
Metal.
IP Rating
TBC.
Weight
4.5kg (no batteries).
Operating conditions/temperature
-5ºC to +40ºC. Max relative humidity: 95%.
Network specification
Max. no. of Repeaters per Main XFP: 8 (any mix); Max. total length of Repeater network: 500m; Cabling requirements: 1.5mm2 two core screened fire resistant. Network is non-redundant.
Datasheet