1SFA898111R7000

PSTX170-600-70 Softstarter (PSTX170-600-70)

Trade Price

£3,655.37

Per

1

Unit

EA

Pack Quantity

1

1SFA898111R7000
1SFA898111R7000
1SFA898111R7000
1SFA898111R7000

Information

The softstarter PSTX170-600-70 has a rated maximum operational current of 170 A with an operating voltage span from 208...600 V AC. The rated control voltage is between 100...250 V AC at 50/60 Hz. PSTX features a three-phase control soft start and stop through a voltage or a torque ramp. It has built-in bypass for easy installation and energy saving. A RUN, TOR and Event signal is available from relay outputs in NO (normally open state). The PSTX has functions such as current limit, kickstart, analog output, EOL, motor heating and pump cleaning. PSTX also features features jog, braking, stand-still brake, diagnostics, sequence start and emergency/fire pump mode as standard.To interact with PSTX, it has a detachable full graphic display with IP66 and 4x outdoor rating. There are four ways to communicate with PSTX. It can be done by hardwire inputs Start/Stop/Reset of fault, and by three programmable digital inputs. Another popular option is the built-in Fieldbus communication Modbus RTU and incl optional ANYBUS modules with every major protocol such as for example Profinet, Profibus, Modbus TCP, Ethernet IP and others. Another way to communicate with PSTX is to use an external adaptor and a Fieldbus plug. PSTX is the complete alternative for any motor starting application. It’s suitable for medium to large-sized three-phase motors with nominal currents from 30...1250 A inline connection or 52...2160 A inside delta connection. Typical applications are, for example, pumps, fans, compressors, and conveyors.

Technical Specifications

Minimum Order Quantity:

1 piece

Customs Tariff Number:

85371091

Product Net Width:

199 mm

Product Net Height:

377 mm

Product Net Depth / Length:

283 mm

Product Net Weight:

8.9 kg

Rated Operational Voltage:

208 ... 600 V AC

Rated Control Supply Voltage (Us):

100 ... 250 V AC

Rated Control Circuit Voltage (Uc):

24 V DC

Rated Frequency (f):

50/60 HzMain Circuit 50 / 60 Hz

Rated Operational Power - In-Line Connection (Pe):

(230 V) 45 kW(400 V) 90 kW(500 V) 110 kW

Rated Operational Current - In-Line Connection (Ie):

170 A

Rated Operational Power - Inside Delta Connection:

at 230 V 90 kWat 400 V 160 kWat 500 V 200 kW

Rated Operational Current - Inside Delta Connection:

300 A

Service Factor Percentage:

100 %

Overload Protection:

Built-in electronic overload protection

Integrated Electronic Overload:

Yes

Adjustable Rated Motor Current Ie:

30 ... 100 %

Starting Capacity at Maximum Rated Current Ie:

4xIe for 10s

Ramp Time:

1 ... 120 second [unit of time]

Initial Voltage During Start:

10 ... 99 %

Step Down Voltage Special Ramp:

100 ... 10 %

Current Limit Function:

1.5 ... 7.5 xle

Switch for Inside Delta Connection:

Yes

Run Signal Relay:

Yes

By-pass Signal Relay:

Yes

Fault Signal Relay:

Yes

Overload Signal Relay:

Yes

Analog Outputs:

0…10 V, 0…20 mA, 4…20 mA

Signal Indication Ready to Start/Standby ON (LED):

Green

Signal Indication Running R (LED):

Green

Signal Indication Protection (LED):

Yellow

Signal Indication Fault (LED):

Red

Communication:

Modbus-RTU; Modbus-TCP; Ethernet-IP; EtherCAT; DeviceNet; CANopen; Profibus; Profinet; BACnet-IP; BACnet-MSTP

Degree of Protection:

IP00

Terminal Type:

Main Circuit: Bars

Connecting Capacity Main Circuit:

Hole Diameter 8.5 mm

Connecting Capacity Control Circuit:

Rigid 1 x 2.5 mm²

Connecting Capacity Supply Circuit:

Rigid 1 x 2.5 mm²

Tightening Torque:

Main Circuit 14 N·m

Product Main Type:

PSTX170

Function:

Auto phase sequence detectionAutomatic restartCurrent limitCurrent limit rampDual current limitDynamic brakeElectricity meteringElectronic overload Time-to-coolEmergency modeEvent logFull voltage startJog with slow speed, forward and reverseKeypad passwordKick startLimp mode with two-phase motor control if one set of thyristors is shortedMotor heatingPre-start functionPump cleaningReal time clockSequence startSoft start with torque controlSoft start with voltage rampSoft stop with torque controlSoft stop with voltage rampStand still brakeStart reverse (external contactors)Thyristor runtime measurementTorque limitVoltage sags detection

Protection Function:

Bypass open protection; Current imbalance protection; Current underload protection; Dual overload (separate overload for start and run); Earth fault protection / ground fault protection; Electronic overload protection, EOL; Extension IO failure protection; Fieldbus failure protection; HMI failure protection; Locked rotor protection; Max number of starts/hour; Over voltage protection; Phase reversal protection; Power factor underload protection; PT-100 connection; PTC connection; Too long current limit protection; Too long start time protection; Under voltage protection; User defined protection; Voltage imbalance protection

Warning Details:

Current imbalance warning; Current underload warning; Electronic overload Time-to-trip; EOL warning; Faulty fan warning; Locked rotor warning; Motor runtime limit warning; Over voltage warning; Phase loss warning (for standby); Power factor underload warning; Short circuit warning (for Limp mode); THD(U) - Total Harmonic Distortion warning; Thyristor overload warning (SCR); Under voltage warning; Voltage imbalance warning

Maximum Operating Voltage UL/CSA:

Main Circuit 600 V

Tightening Torque UL/CSA:

Main Circuit 123.9

Ambient Air Temperature:

Operation -25 ... +60 °CStorage -40 ... +70 °C

RoHS Status:

Following EU Directive 2002/95/EC August 18, 2005 and amendment

Package Level 1 Width:

263 mm

Package Level 1 Depth / Length:

323 mm

Package Level 1 Height:

454 mm

Package Level 1 Gross Weight:

10.4 kg

Package Level 1 EAN:

7320500501436

Package Level 1 Units:

box 1 piece

Object Classification Code:

Q

ETIM 7:

EC000640 - Soft starter

ETIM 8:

EC000640 - Soft starter

ETIM 9:

EC000640 - Soft starter

eClass:

V11.0 : 27370907

UNSPSC:

39121521

IDEA Granular Category Code (IGCC):

4740 >> Soft starter

Document Links