Trade Price
£308.92
Per
1
Unit
EA
Pack Quantity
1
Type CM-IWS insulation monitoring relay * Easy connect technology * Double-chamber cage connection terminals * LEDs for status indication * Integrated marker label * Sealer transparent cover * Snap-On housing
EAN
4016779852647
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Product Net Width
22.5 mm
Product Net Height
85.6 mm
Product Net Depth / Length
103.7 mm
Product Net Weight
0.137 kg
Function
Unearthed AC systemsUnearthed DC systemsUnearthed mixed AC / DC systemsUp to 250 V ACUp to 300 V DC
Measuring Range
1 ... 100 kΩ
Rated Control Supply Voltage (Us)
24 ... 240 V AC/DC
Rated Frequency (f)
Measuring Circuit 15 ... 400 Hz
Output
1 c/o (SPDT) contact
Terminal Type
Screwless Terminals
Rated Operational Current AC-12 (Ie)
(230 V) 4 A
Rated Operational Current AC-15 (Ie)
(230 V) 3 A
Rated Operational Current DC-12 (Ie)
(24 V) 4 A
Rated Operational Current DC-13 (Ie)
(24 V) 2 A
Minimum Switching Capacity
24 V10 mA
Rated Impulse Withstand Voltage (Uimp)
Measuring Circuit / Output Circuit 6 kVSupply Circuit / Measuring Circuit 6 kVSupply Circuit / Output Circuit 6 kV
Rated Insulation Voltage (Ui)
Measuring Circuit / Output Circuit 300 VSupply Circuit / Measuring Circuit 300 VSupply Circuit / Output Circuit 300 V
Degree of Protection
Housing IP50Terminals IP20
Overvoltage Category
III
Pollution Degree
3
Short-Circuit Protective Devices
Output Circuit NC - F Type Fuses 6 AOutput Circuit NO - F Type Fuses 10 A
System Leakage Capacitance (CE)
10 µF
Electrical Durability
AC-12 100000 cycle
Mechanical Durability
30000000 cycle
Connecting Capacity
Flexible with Ferrule 2x 0.5 ... 1.5 mm²Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm²Flexible 2x 0.5 ... 1.5 mm²Rigid 2x 0.5 ... 1.5 mm²
Wire Stripping Length
8 mm
Recommended Screw Driver
0.8 x 4
Mounting Position
1 ... 6
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Standards
CAN/CSA C22.2 No.14IEC/EN 63000IEC/EN 61326-2-4IEC/EN 61557-1IEC/EN 61557-8UL 508
Maximum Operating Voltage UL/CSA
Output Circuit 300 V AC
Contact Rating UL/CSA
B300
Connecting Capacity UL/CSA
Flexible 2x 18-16 AWGRigid 2x 20-16 AWG
Pilot Duty UL/CSA
B300
Flammability According to UL94
V-0
Ambient Air Temperature
Operation -25 ... +60 °CStorage -40 ... +85 °C
Maximum Operating Altitude Permissible
Without Derating 2000 m
RoHS Status
Following EU Directive 2011/65/EU
Package Level 1 Units
box 1 piece
Package Level 1 Width
97 mm
Package Level 1 Depth / Length
30 mm
Package Level 1 Height
109 mm
Package Level 1 Gross Weight
0.162 kg
Package Level 1 EAN
4016779852647
Object Classification Code
B
ETIM 7
EC001444 - Insulation and earth fault monitoring relay
ETIM 8
EC001444 - Insulation and earth fault monitoring relay
ETIM 9
EC001444 - Insulation and earth fault monitoring relay
eClass
V11.0 : 27371807
UNSPSC
39122331
E-Number (Finland)
2712259
E-Number (Sweden)
3860659
Datasheet