Trade Price
£618.12
Per
1
Unit
EA
Pack Quantity
1
Number of poles
3 P
Complete device with protection unit
Yes
Trip Unit
TM A/A
Integrated earth fault protection
No
Number of modules
6
Rated operational voltage Ue
220 / 690 V
Frequency
50/60 Hz
Rated insulation voltage
800 V
Rated impulse withstand voltage
8 kV
With under voltage release
No
Rated current
20 A
Rated ultimate short-circuit breaking capacity Icu under 690V AC IEC 60947-2
7.5 kA
Thermal protection nob setting xIN
0.63 / 0.8 / 1
Breaking capacity on 1 pole for IT 230V NF 60947-2
51 kA
Breaking capacity on 1 pole for IT 400V NF 60947-2
9 kA
Rated service breaking capacity Ics AC according IEC 60947-2
50 %
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2
35 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2
35 kA
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2
30 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2
30 kA
Rated ultimate short-circuit breaking capacity Icu under 440V AC IEC 60947-2
50 kA
Correction factor of rating current for 2 devices placed side-by-side
1
Correction factor of rating current for 3 devices placed side-by-side
1
Correction factor of rating current for 4 and 5 devices placed side-by-side
1
Correction factor of rating current for 6 devices placed side-by-side
1
Total power loss under IN
18.5 W
Power loss per pole at In
6.2 W
Tripmode
TM
Thermal protection trip time
0 ms
Time of response when opening
20 ms
Magnetic trip delay time
0 ms
Electric endurance in number of cycles
1000
Number of mechanical operations
4000
DIN rail mounting with optional adaptator
No
Connection cross-sect. flexible conductor
35 / 150mm²
Type of connection
Terminal
Range of the magnetic adjustment
120 / 160 / 200 / 240 A
Magnetic protection nob setting xIN
6 / 8 / 10 / 12
Setting type In or Ith
IN
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Motor drive optional
Yes
European directive WEEE
concerned
Protection index IP
IP4X
Operating temperature
-25…70 °C
Altitude
2000 m
Air humidity protection
for all climates
Storage/transport temperature
-35…70 °C
Datasheet