3WL1220-4EG47-1CB4-Z

withdrawable circuit breaker with guide frame 4-pole, size II, IEC In=2000A to 690V, AC50/60Hz Icu=100kA at 500V rear connection vertical Overcurrent release ETU 45 LSING protection adjustable 0.4-1 in with cubicle bus and Ground fault protection Opt.: Comm./measuring func./ZSS With manual operating mechanism with storage with mechanical request With 1st auxiliary release Shunt release "F", F1 30 V DC, 100% ON period With 2nd auxiliary release "F", F2 Shunt release 24 V DC; 100% on-load factor 4NO+4NC F23= Internal current converter 4-pole switch BGII K07= Tripped signaling contact, 1 CO not possible with option F02 M21= Switch-on solenoid 24 V DC 100% on-load factor R16= Position signaling switch, withdrawable part 6 changeover contacts R21= Shutter 2-part can be locked with bracket lock R30= Locking device against opening of the Control cabinet door R55= Mutual mechanical interlock for switch with frame 2 m T40= Door sealing frame