3WL1340-4EG46-1FA2-Z

withdrawable circuit breaker with guide frame 4-pole, size III, IEC In=4000A to 690V, AC50/60Hz Icu=100kA at 500V rear connection horizontal Overcurrent release ETU 45 LSING protection adjustable 0.4-1 in with cubicle bus and Ground fault protection Opt.: Comm./measuring func./ZSS With manual operating mechanism with storage with mechanical request With 1st auxiliary release Shunt release "F", F1 50/60 Hz 110 V AC/110 V DC, 100% on-load factor without 2nd auxiliary release 2NO+2NC C11= Electrical On with sealing cap not possible with option F02 C22= Ready-to-close signaling K07= Tripped signaling contact, 1 CO not possible with option F02 M06= Motor drive, Drive motor AC 50/60 Hz 208-240 V or 220-250 V DC M25= Switch-on solenoid 110-127 V AC/110-125 V DC, 100% on-load factor P23= Retrofitted to Connection: Top horizontal, bottom vertical R15= Position signaling switch, withdrawable part 3 changeover contacts R21= Shutter 2-part can be locked with bracket lock T40= Door sealing frame

Trade Price

£32,517.38

Per

1

Unit

EACH

Pack Quantity

1

3WL1340-4EG46-1FA2-Z

Document Links

Datasheet