withdrawable circuit breaker with guide frame 4-pole, size II, IEC In=3200A to 690V, AC50/60Hz Icu=80kA at 500V rear connection vertical Overcurrent release ETU 25 LSI protection adjustable 0.4-1 in With manual operating mechanism with storage with mechanical request With 1st auxiliary release Shunt release "F", F1 30 V DC, 100% ON period without 2nd auxiliary release 2NO+2NC R21= Shutter 2-part can be locked with bracket lock R68= RONIS locking device against unauthorized closing S05= Fortress locking device in Off position Disconnector condition Safe Off/disconnector function T40= Door sealing frame