withdraw. non-aut. circuit-b. with guide frame 3-pole, size II, IEC In=1600A to 690V, AC50/60Hz Icu=80kA at 500V rear connection horizontal without overcurrent release Motorized/manual operating mechanism with spring charging motor AC 50/60 Hz 110-127 V AC or 110-125 V DC Activation 50/60 Hz 110 V AC, 110 V DC With 1st auxiliary release Shunt release "F", F1 50/60 Hz 110 V AC/110 V DC, 100% on-load factor without 2nd auxiliary release 4NO+4NC C20= Spring charge status indicator not possible with option F02 C22= Ready indicator R21= Shutter 2-part can be locked with padlock S05= Fortress locking device in Off position (safe OFF/disconnector functionality) Disconnector condition in compliance with IEC 60947-2