3WL1112-3CB46-6BN4-Z

withdrawable circuit breaker with guide frame 4-pole, size I, IEC In=1250A to 690V, AC50/60Hz Icu=66kA at 500V rear connection horizontal Overcurrent release ETU 25 LSI protection adjustable 0.4-1 in Motorized/manual operating mechanism with spring charging motor 24-30 V DC Activation 24 V DC With 1st auxiliary release Shunt release "F", F1 24 V DC; 100% ON period With 2nd auxiliary release "R", F3 Undervoltage, instant. 208-240 V AC, 220-250 V DC 4NO+4NC B06= Rated current reference module 630 A for ETU25, 27, 45, 55, 75, 76 for setting rated current in K07= Tripped signaling contact, 1 CO not possible with option F02 P23= Retrofitted to Connection: Top horizontal, bottom vertical R15= Position signaling switch, withdrawable part 3 changeover contacts R21= Shutter 2-part can be locked with bracket lock R55= Mutual mechanical interlock for switch with frame 2 m

Trade Price

£9,626.19

Per

1

Unit

EACH

Pack Quantity

1

3WL1112-3CB46-6BN4-Z

Document Links

Datasheet