Trade Price
£545.17
Per
1
Unit
EA
Pack Quantity
1
VigiPacT RHU is a front panel mounting communicating residual current protection relay. It protects against people direct or indirect contact, property fire hazards and motors. It measures the earth leakage current in an electrical installation via its associated toroid. It trips the associated circuit breaker when the set residual operation current is overrun. It can activate an alarm and a pre-alarm. The operational supply voltage is 220/240VAC 50/60Hz. It is a type A earth-leakage protection class. The current sensitivity is from 30mA to 30A. The time delay is adjustable from 0 to 4.5s. It is installed on a front panel switchboard and the protection degree is IP40. It must be associated with a compatible Schneider Electric type A toroid or rectangular sensor. It complies with IEC 60755, IEC 60947-2 annex M and IEC 60947-5-1 standards. RUH is integrated in the Smart Panel architecture with the Modbus communication.
Range
VigiPacT
Device short name
RHU
Product or component type
Residual current protection relay
Relay application
Monitoring relay Protection relay
mounting support
Front panel
Earth-leakage protection class
Type A
Type of setting
Modbus address Keypad
Residual earth-leakage sensitity adjustment type
Adjustable
Earth-leakage sensitivity
0.03…1 A, adjustable in step of 0.001 A 1…30 A, adjustable in step of 0.1 A
Earth-leakage time delay
Instantaneous for 0.03 A Adjustable 0…4.5 s for 0.03…30 A adjustable in step of 10 ms
Threshold setting
0.015...1 A adjustable in step of 0.001 A pre-alarm 1...30 A adjustable in step of 0.1 A pre-alarm 0.03...1 A adjustable in step of 0.001 A alarm 1...30 A adjustable in step of 0.1 A alarm
Current sensors compatibility
VigiPacT TOA earth leakage current sensor VigiPacT A earth leakage current sensor VigiPacT L earth leakage current sensor
[Ithe] conventional enclosed thermal current
8 A
Minimum load
10 mA at 12 V
[Us] rated supply voltage
220...240 V AC 50/60 Hz 70...110 %
Power consumption in VA
8 VA
Monitored distribution system
1000 V - AC at 50/60 Hz (maximum) 1000 V - AC at 400 Hz (maximum)
Earthing system
TT TN-S IT
[Uimp] rated impulse withstand voltage
8 kV
Reset
Remote reset
Test function
Remote test Remote test (via communication) Local
Signal contacts composition
1 C/O alarm fail-safe 1 NO pre-alarm fail-safe
Type of measurement
Earth fault current internal measurement, range: 20...200 %, accuracy: +/- 20 %
Refresh time
0.5 s
Communication service
Modbus slave
Tamperproof of settings
Protected by access code
Connections - terminals
Alarm circuit: terminal block cable(s) 0.2…2.5 mm² flexible AWG 22...AWG 12 Alarm circuit: terminal block cable(s) 0.2…2.5 mm² rigid AWG 22...AWG 12 Relay test and fault reset: terminal block cable(s) 0.2…2.5 mm² flexible AWG 22...AWG 12 Relay test and fault reset: terminal block cable(s) 0.2…2.5 mm² rigid AWG 22...AWG 12 Sensor: terminal block cable(s) 0.2…2.5 mm² flexible AWG 22...AWG 12 Sensor: terminal block cable(s) 0.2…2.5 mm² rigid AWG 22...AWG 12 Voltage presence: terminal block cable(s) 0.2…2.5 mm² flexible AWG 22...AWG 12 Voltage presence: terminal block cable(s) 0.2…2.5 mm² rigid AWG 22...AWG 12 Power supply: terminal block cable(s) 0.2…2.5 mm² flexible AWG 22...AWG 12 Power supply: terminal block cable(s) 0.2…2.5 mm² rigid AWG 22...AWG 12 Pre alarm: terminal block cable(s) 0.2…2.5 mm² flexible AWG 22...AWG 12 Pre alarm: terminal block cable(s) 0.2…2.5 mm² rigid AWG 22...AWG 12
Wire stripping length
Alarm circuit: 6 mm Relay test and fault reset: 6 mm Sensor: 6 mm Voltage presence: 6 mm Power supply: 6 mm Pre alarm: 6 mm
Tightening torque
Alarm circuit: 0.5 N.m Relay test and fault reset: 0.5 N.m Sensor: 0.5 N.m Voltage presence: 0.5 N.m Power supply: 0.5 N.m Pre alarm: 0.5 N.m
Standards
EN/IEC 60947-2 Annex M EN/IEC 60755 UL 1053 CAN/CSA C22.2 No. 144
Width
72 mm
height
72 mm
Depth
117 mm
Cut-out dimensions
68 x 68 mm
Net weight
0.3 kg
IP degree of protection
IP40 front face: conforming to IEC 60529 IP30 other parts: conforming to IEC 60529 IP20 connection: conforming to IEC 60529
IK degree of protection
IK07 conforming to EN 50102
Mechanical robustness
Vibrations 13.2...100 Hz: 0.7 g Vibrations 2...13.2 Hz: +/- 1 mm
Environmental characteristic
Exposure to damp heat not in service conforming to IEC 60068-2-30 Exposure to damp heat in service conforming to IEC 60068-2-56 Salt mist conforming to IEC 60068-2-52
Overvoltage category
IV
Electrical shock protection class
Class II
Electromagnetic compatibility
Conducted and radiated emissions: , B, conforming to CISPR 11 Conducted radio-frequency immunity test: , 3, conforming to IEC 61000-4-6 Electrostatic discharge immunity test: , 4, conforming to IEC 61000-4-2 High-energy conducted susceptibility: , 4, conforming to IEC 61000-4-5 Low-energy conducted susceptibility: , 4, conforming to IEC 61000-4-4 Radiated susceptibility: , 3, conforming to IEC 61000-4-3
Relative humidity
95 % at 55 °C
Pollution degree
3 conforming to IEC 60664-1
ambient air temperature for operation
-25…55 °C
Ambient air temperature for storage
-40…85 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
8.5 cm
Package 1 Width
11.0 cm
Package 1 Length
15.5 cm
Package 1 Weight
430.0 g
Unit Type of Package 2
S04
Number of Units in Package 2
24
Package 2 Height
30.0 cm
Package 2 Width
40.0 cm
Package 2 Length
60.0 cm
Package 2 Weight
11.086 kg
Warranty
18 months