1SFL637025R6811

GAF750-10-11 24-60V DC Contactor

Trade Price

£5,209.31

Per

1

Unit

EA

Pack Quantity

1

1SFL637025R6811

Information

GAF460...GAF750 3 pole contactor - 250 to 1750A DC-1 AC/DC operated 1NO+1NC aux * Part number: GAF750-10-11 * GAF185 ... GAF2050 contactors are designed for controlling resistive or slightly inductive loads up to 1000 V DC. * These contactors are of the block type design with 3 main poles for connection in series by the user according to conductor cross-sectional area or by using LP connection bars to be ordered separately. * Equipped with low voltage inputs for control, for example a PLC.

Technical Specifications

Minimum Order Quantity

1 piece

Customs Tariff Number

85364900

Product Net Width

210 mm

Product Net Depth / Length

242 mm

Product Net Height

283 mm

Product Net Weight

14 kg

Number of Main Contacts NO

1

Number of Main Contacts NC

0

Number of Auxiliary Contacts NO

1

Number of Auxiliary Contacts NC

1

Rated Operational Voltage

Main Circuit 1000 V

Conventional Free-air Thermal Current (Ith)

acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 1050 A

Rated Operational Current DC-1 (Ie)

(1000 V) 3 Poles in Series, 40 °C 1050 A(1000 V) 3 Poles in Series, 55 °C 875 A(1000 V) 3 Poles in Series, 70 °C 720 A(220 V) 3 Poles in Series, 40 °C 1050 A(220 V) 3 Poles in Series, 55 °C 875 A(220 V) 3 Poles in Series, 70 °C 720 A(400 V) 3 Poles in Series, 40 °C 1050 A(400 V) 3 Poles in Series, 55 °C 875 A(400 V) 3 Poles in Series, 70 °C 720 A(600 V) 3 Poles in Series, 40 °C 1050 A(600 V) 3 Poles in Series, 55 °C 875 A(600 V) 3 Poles in Series, 70 °C 720 A

Rated Insulation Voltage (Ui)

acc. to UL/CSA 1000 V

Rated Impulse Withstand Voltage (Uimp)

Main Circuit 8 kV

Mechanical Durability

3 million

Maximum Mechanical Switching Frequency

300 cycles per hour

Coil Operating Limits

(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ <= 70 °C)

Rated Control Circuit Voltage (Uc)

DC Operation 24 ... 60 V

Coil Consumption

Holding at Max. Rated Control Circuit Voltage 50 Hz 12 V·AHolding at Max. Rated Control Circuit Voltage 60 Hz 12 V·AHolding at Max. Rated Control Circuit Voltage DC 4.5 WPull-in at Max. Rated Control Circuit Voltage 50 Hz 850 V·APull-in at Max. Rated Control Circuit Voltage 60 Hz 850 V·APull-in at Max. Rated Control Circuit Voltage DC 950 V·A

Connecting Capacity Main Circuit

Bar 52 mm²Rigid Al-Cable 300 mm²Rigid Cu-Cable 300 mm²

Connecting Capacity Auxiliary Circuit

Flexible with Ferrule 1x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²Flexible 2x0.75 ... 2.5 mm²Solid 2 x 1 ... 4 mm²Stranded 2 x 1 .... 4 mm²

Degree of Protection

acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00

Terminal Type

Main Circuit: Bars

Maximum Operating Voltage UL/CSA

Main Circuit 600 V

General Use Rating UL/CSA

(1000 V DC) 900 A(440 V DC) 900 A(600 V DC) 900 A

Ambient Air Temperature

Operation -40 ... +80 °CStorage -40 ... +70 °C

Maximum Operating Altitude Permissible

Without Derating 3000 m

Resistance to Shock acc. to IEC 60068-2-27

Shock Direction: A 5 gShock Direction: B1 5 gShock Direction: B2 5 gShock Direction: C1 5 gShock Direction: C2 5 g

RoHS Status

Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Package Level 1 Units

box 1 piece

Package Level 1 Width

280 mm

Package Level 1 Depth / Length

375 mm

Package Level 1 Height

310 mm

Package Level 1 Gross Weight

15 kg

Package Level 1 EAN

7320500400838

Object Classification Code

Q

ETIM 4

EC002552 - Power contactor, DC switching

ETIM 5

EC002552 - Power contactor, DC switching

ETIM 6

EC002552 - Power contactor, DC switching

ETIM 7

EC002552 - Power contactor, DC switching

ETIM 8

EC002552 - Power contactor, DC switching

eClass

V11.0 : 27371018

UNSPSC

39121529

IDEA Granular Category Code (IGCC)

4763 >> Power contactor, DC switching

Document Links

Catalogue page

Datasheet